Company fined after dad of Bradley Lowery suffered serious burns while carrying out work
and on Freeview 262 or Freely 565
A company has been fined after a Bradley Lowery's father sustained serious burns to his body while working for them.
Advertisement
Hide AdAdvertisement
Hide AdCarl Lowery had been working on new apartment blocks at The Crescent, Hulme Street, Salford when an electrical flash blew him backwards and burnt his arms and face on 12 May 2020.
The then 37-year-old underwent multiple surgeries following the incident and required a skin graft from his thigh.
The incident happened almost three years after Carl lost his son Bradley to a rare form of cancer.
Advertisement
Hide AdAdvertisement
Hide AdAlong with his wife Gemma, Carl established the Bradley Lowery Foundation, which helps families that are fundraising to obtain medical equipment and treatment.
Carl, now 41, had been working alongside a colleague at SRE Cabling and Jointing Limited, with the company sub-contracted by Aberla M&E Limited to carry out cabling and jointing works on the new apartments.
The pair were working on the building’s main switchboard, with nearby bus bars left live with electricity and covered by a guard panel.
Advertisement
Hide AdAdvertisement
Hide AdHowever, a gap in the guard panel led to a nut rolling behind and coming into contact with the live bus bars, causing an electrical flash which blew Carl backwards and burnt his arms and face.
A Health and Safety Executive (HSE) investigation into this incident found Aberla M&E Limited had incorrectly assumed the guard panel was sufficient separation of the workers from the live bus bars.
It said the company failed to take into account a gap in the guard panel, which risked nuts, bolts, tools and even fingers coming into contact with the bus bars.
Advertisement
Hide AdAdvertisement
Hide AdThere was also a failure to issue a permit to work (PTW) on or near live components, which resulted in the main switchboard being left live, it said.
There was also a distinct lack of live works monitoring by the company, with the electrical site manager rarely visiting the work area, it said.
Carl said in his victim personal statement: “Even when Bradley was poorly, I worked. I’ve not been able to work since the accident either, mentally or physically.
Advertisement
Hide AdAdvertisement
Hide Ad“My left hand is my dominant hand and after the accident I had no grip. I had to try and learn how to use my non-dominant hand.”
HSE guidance states employers must produce a risk assessment prior to working with electricity.
The risk assessment must cover who could be harmed by electrical hazards, how the level of risk has been established and the precautions taken to control the risk.
More on this can be found at: Electrical safety - HSE
Advertisement
Hide AdAdvertisement
Hide AdAberla M&E Limited, of The Parklands, Bolton, Greater Manchester, pleaded guilty to breaching Section 3(1) of the Health and Safety at Work etc. Act 1974. The company was fined £40,000 and ordered to pay £20,000 in costs at Manchester Magistrates’ Court on 14 March 2024.
HSE inspector Lisa Bailey said: “This incident has had life-changing consequences for Carl and his family. It could have been avoided if the company had actively monitored and managed procedures, to identify risks and prevent incidents.
“Working with electricity is a high-risk activity and safety must be a priority. Proper planning to ensure that risks are eliminated at system design stage is essential.”